Cracking of PMG Capacitor Cases Due to Prolonged Elevated Temperatures in Certain High Voltage Generators (Kato). Caterpillar


`
Cracking of PMG Capacitor Cases Due to Prolonged Elevated Temperatures in Certain High Voltage Generators (Kato). [TIBU3821]
GENERATORS
GENERATOR GP
Cracking of PMG Capacitor Cases Due to Prolonged Elevated Temperatures in Certain High Voltage Generators (Kato).

CONFIDENTIAL TIBU3821-00

TECHNICAL INFORMATION BULLETIN

April 02, 2003

High Voltage Generators on AVSpare Gensets

24Z, 25Z, 7RN, 8RM, 2JW, 6HN, 6WN, BPJ, BRK, CMC, CMD, CMJ, CMB, CMJ, CNB, CRN, CSZ, CWW, CWY, FDN, PPS

 

Component Code: 1404

SUBJECT: Cracking of PMG Capacitor Cases Due to Prolonged Elevated Temperatures in Certain High Voltage Generators (Kato)

PROBLEM:

The PMG capacitors installed in certain AVSpare high voltage generators (Kato SR4B-HV 12 and 13 kV generators) may develop cracks on the surface of the capacitor body. These capacitors are installed in the generator exciter under the side cover. On generator frame sizes 2410 through 2480, the capacitors are located above the space heaters. This proximity to the space heaters along with site conditions and high ambient temperature make heat-related failure the leading suspect. These capacitors, when needed, aid in providing a low impedance power source for proper voltage regulator operation. In most cases the generator will operate satisfactorily with a cracked capacitor or without capacitors. Only in the case of shorted capacitors will the generator fail to operate.

SOLUTION:

This problem continues to be investigated by AVSpare and the generator supplier. In the interim, AVSpare recommends the following procedure:

 

  1. Inspect the generator PMG capacitors (Cat p/n 161-4498 Capacitor) at the first scheduled maintenance interval.
  2. Turn off the generator space heater. Avoid coming in contact with hot surfaces when working in the generator exciter area.
  3. Remove the exciter side cover. See the Illustration 1 for the typical capacitor location.
  4. Cut the tie-wraps securing the capacitors to the bracket and inspect each capacitor.
  5. Rotate the capacitors by hand and look for any large cracks in the black plastic body of the capacitor.
  6. If the cracked capacitors are found, and if the SR4B High Voltage Generator is using the KCR 760 regulator, disconnect and remove the capacitors.

 

 

Illustration 1. Typical capacitor loction.

PMG capacitors are not necessary for satisfactory operation. Replacement of the cracked capacitors with new capacitors of the same design is likely to lead to similar failures. The SR4B-HV generators have been tested while using a KCR 760 voltage regulator. The tested generators operated satisfactorily both with and without the capacitors across the PMG. Additional tests are being conducted on SR4B-HV generator using a Basler DECS regulator to verify the performance of this combination.

Note: In order to be consistent, the AVSpare supplier installed capacitors on their entire line of PMG generators and voltage regulators. Due to the wide variety of voltage regulators and generator designs that they produce, these capacitors were installed regardless of whether they were necessary for system operation.

 

COPYRIGHT 2003 AVSpare
ALL RIGHTS RESERVED

Information System:

The Navigator Touchscreen Display Can Remain in a Black Screen State when the �Power On� LED Is Illuminated
New Steering Cylinders have Collar Assemblies on Rods
Use of the 9Y-5710 Auxiliary Sea Water Pump in 3500 and 3500B applications
THE AUTOMATIC LUBRICATION SYSTEM REQUIRES AN ADDITIONAL ORIFICE
Landfill Compactor Wheel Tip Clearance
MODIFICATION TO PREVENT OIL BLOWING THROUGH THE 165-8460 VENT AS.
Flashing New Software When Electronic Control Module (ECM) or Injectors Are Replaced
NEW CRANKSHAFT SEALS FOR THE FRONT AND FOR THE REAR ARE NOW IN PRODUCTION BUT ARE NOT AVAILIBLE TO BE OREDERD AT THIS TIME
A NEW INJECTION ACTUATION PRESSURE CONTROL VALVE CONNECTOR INCREASES ENGINE OPERATION
FAULT CODE MAY APPEAR WHILE PERFORMING PI10199
THE WHEEL SPINDLES MAY FAIL ON CERTAIN 216 AND 226 SKID STEER LOADERS
Fuel Level Sensors May Break Loose From Float Arm
Loose Connections on Voltage Regulators Can Lead to Above Normal Voltage Output and Regulator Failure
Improvements To The Heating Ventilating And Air Conditioning (HVAC) System Increase Operator Comfort
PRIMER/PAINT ON THE FINISHED SURFACE OF CYLINDER RODS FOR SOME WORK TOOLS
Water Pump Leak on 797 Trucks
Fan Reversing Valve Failures
Heat Shield Modification Can Extend the Life of the Center Valve Cover Seal
Troubleshooting Exhaust Gas Leaks That May Contribute to Excessive Engine Compartment Temperatures and Soot Accumulation
Loose Counter Weights Can Cause Banging Noise When Turning
SOS PARTICLE COUNT LIMITS FOR THE FAIRFIELD DRIVE IS HIGHER THAN THE LIMITS FOR OTHER CATERPILLAR MACHINES
INTERFERENCE BETWEEN THE LIFT ARMS & CERTAIN WORK TOOLS
Air Filter Restricted Indictor May Illuminate at Low Hours or with Clean Filters
MODIFICATIONS ARE NECESSARY IN ORDER TO USE THE 165-9889 BROOM BRACKET GP ON ALPHA XR MACHINES