Customer specified parameters allow the engine to be configured to the exact needs of the application.
Customer parameters may be changed repeatedly as a customer's operation changes.
The following information is a brief description of the customer specified parameters. The following parameter values are included with the descriptions:
- Minimum
- Maximum
- Default
The rating number is the selected rating within a power rating family. The flash file defines the power rating family. The flash file can contain one to four ratings. The rating number defines the power rating that is used within the power rating family.
Minimum | Maximum | Default |
---|---|---|
1 | 4 | 1 |
The "Low Idle Speed" is the minimum engine rpm.
Minimum | Maximum | Default |
---|---|---|
700 rpm | 1200 rpm | 1200 rpm |
The "High Idle Speed" is the maximum engine rpm.
Minimum | Maximum | Default |
---|---|---|
1900 rpm | 2900 rpm | 2310 rpm |
"Equipment ID" is the identification of the equipment that is assigned by the customer. The "Equipment ID" is only for reference only by the customer. The "Equipment ID" is not required by the Electronic Control Module (ECM).
Value | Default |
---|---|
17 digits
The available characters are dependent on the service tool that is being used. |
Not programmed |
"Monitoring Mode Shutdowns" controls the shutdown feature that is associated with the engine monitoring feature. When this feature is enabled and an event code with a "-3" suffix is detected, the engine will be shut down.
Value | Default |
---|---|
Disabled
Enabled |
Disabled |
"Monitoring Mode Derates" controls the derate that is associated with the engine monitoring feature. When this feature is enabled and an event code with a "-2" is detected, the engine will be derated.
Value | Default |
---|---|
Disabled
Enabled |
Enabled |
Limp Home Desired Engine Speed
The "Limp Home Desired Engine Speed" is the maximum speed of the engine when the engine has been derated.
Minimum | Maximum | Default |
---|---|---|
700 rpm | 1800 rpm | 1200 rpm |
J1939 Continuous Fault Handling
Remote Torque Speed Control Enable Status
The "Remote Torque Speed Control Enable Status" parameter determines the way that faults will be handled by the ECM when the "J1939 Torque Speed Control (TSC1)" message is used as a speed request input to the ECM. Programming the "Remote Torque Speed Control Enable Status" to "Enabled" will cause the ECM to display a fault code if a valid TSC1 message is not received by the engine ECM within 30 seconds of the engine starting. If the" Remote Torque Speed Control Enable Status" is programmed to "Disabled", the engine will display a 247-12 Data Link Malfunction immediately after a loss of a TSC1 message. Program "Remote Torque Speed Control Enable Status" to "Enabled" if the ECM will always be receiving a TSC1 message.
Value | Default |
---|---|
Disabled
Enabled |
Disabled |
A coolant level sensor is an optional switch input. Programming the "Coolant Level Sensor" parameter to "Enabled" notifies the ECM that a coolant level sensor input is present on pin J1:38. If this parameter is programmed to "Enabled" and the coolant level falls below the measured level, a "E2143-3" event code will be displayed.
Value | Default |
---|---|
Installed
Not Installed |
Not Installed |
Air Filter Restriction Switch Installation Status
An "Air Filter Restriction Switch" is an optional switch input. Programming the "Air Filter Restriction Switch Installation Status" parameter to "Enabled" notifies the ECM that an input from the air filter restriction switch is present on pin J1:47. When this parameter is programmed to "Enabled" and the air filter restriction switch closes, an E172-1 or J107-15 event code will be displayed.
Value | Default |
---|---|
Installed
Not Installed |
Not Installed |
Fuel/Water Separator Switch Installation Status
A fuel/water separator switch is an optional switch input. Programming the "Fuel/Water Separator Switch Installation Status" parameter to "Enabled" notifies the ECM that a fuel/water separator switch input is present on pin J1:44. When this parameter is programmed to "Enabled" and the fuel/water separator switch closes, an E232-1 or J97-15 event code will be displayed.
Value | Default |
---|---|
Installed
Not Installed |
Not Installed |
User Defined Switch Installation Status
A user defined shutdown switch is an optional switch input. Programming the "User Defined Switch Installation Status" parameter to "Enabled" notifies the ECM that a user defined switch input is present on pin J1:48. If this parameter is programmed to "Enabled" and the user defined shutdown switch closes, the engine will shut down.
Value | Default |
---|---|
Installed
Not Installed |
Not Installed |